Siemens SIRIUS 3RT2028-1BE80 — S0 Power Contactor, 80 VDC Coil
Switching Capacity and Duty Ratings
At 24 VDC the contactor switches 10 A; at 48 V and 60 VDC it switches 2 A; at 110 VDC it switches 1 A; at 125 VDC it switches 0.9 A; at 220 VDC it switches 0.3 A; at 400 VDC it switches 3 A. These DC ratings are the load-break limits — for motor loads the AC-3 maximum operating frequency is 750 switching cycles per hour, while AC-4 duty (plugging/inching) is limited to 250 cycles per hour.
Coil and Timing
The coil is rated at 80 VDC with an initial pull-in value of 0.8 times rated and a full-scale dropout of 1.1 times rated. DC closing time is 15–18 ms; arcing time is 10 ms.
The contactor measures 85 mm high × 45 mm wide × 107 mm deep. Main contact screw size is M4 (16–8 Nm torque range). Conductor cross-section for power circuits: 1–10 mm² solid or stranded.