SIRIUS 3RT2028-1FB40 Power Contactor — Size S0, 24 VDC Coil
The 45 mm width and 85 mm height fit standard S0 contactor footprints; depth is 107 mm.
For AC-1 resistive loads, it handles up to 1,000 cycles per hour. DC switching capacity is specified per voltage: 10 A at 24 V, 2 A at 48 V and 60 V, 1 A at 110 V, 0.9 A at 125 V, and 0.3 A at 220 V. At 400 V AC it switches 3 A. Arcing time is 10 ms, and DC dropout time is 15 to 18 ms. The coil hold-in power factor is 0.8 at rated voltage.
Mounting and Wiring Clearances
Main contact wire range accepts solid or stranded conductors from 1 to 10 mm²; auxiliary contacts accept 2x (0.5 to 1.5 mm²) or 2x (0.75 to 2.5 mm²).