The coil connection uses spring-type terminals — no screwdriver needed for the coil wiring, which speeds panel assembly and avoids loosening from vibration. Rated 5 hp at 230 V, this contactor handles typical three-phase motor starting duty.
Clearance and Wiring
The main contacts accept solid or stranded wire from 1 to 10 mm² (18 to 8 AWG), and the terminals can take two conductors of 0.5 to 2.5 mm² each. Depth is 144 mm, height 102 mm — the Size S0 footprint fits standard 45 mm-wide DIN-rail slots. The arcing time is 10 ms, and the AC coil draws 0.25 A at 50 Hz or 0.28 A at 60 Hz at rated voltage.
The contactor carries no integrated auxiliary switch — if you need aux contacts for feedback or interlocking, they must be added separately.