Its AC-3 rating at 480 V hits 34 A — that's the motor-duty current it handles across starting and running, not just resistive heating.
The 45 mm width and 102 mm height are standard S0 footprint; depth is 144 mm, so factor that into gland-plate clearance and door swing. Keep 10 mm clearance upwards, downwards, and forwards; 6 mm at the sides. That storage range is for handling and shelf life, not running — the operating limit governs in-panel derating.
Switching rates and auxiliary contacts
No built-in auxiliary switch block on this variant — the order code suffix ZX95 means it ships without one. If you need aux contacts for feedback or interlocks, you add a separate block. Switching frequency maxes at 1 000 cycles/hour for AC-1 resistive loads, 750 for AC-3 motor duty, and 250 for AC-4 (plugging/inching). Coil draws 0.25 A at 50 Hz. Arcing time is 10 ms. The auxiliary contact ratings across DC voltages are listed: 6 A at 24 V, 2 A at 48 V and 60 V, 1 A at 110 V, 0.9 A at 125 V, 0.3 A at 220 V, 3 A at 400 V, 0.6 A at 440 V. These matter when you're coordinating control-circuit fuse sizing.