It switches motor loads up to 5 hp at 230 VAC and handles 10 A at 24 VDC for DC loads — the DC-13 curve drops to 0.3 A at 220 VDC, so watch the voltage derating if you're switching solenoids or brakes on a higher DC bus. The included auxiliary switch saves a separate add-on for basic feedback.
The S0 footprint is 45 mm wide, 102 mm tall, 107 mm deep.
Termination & Wiring
For fine-stranded conductors with ferrules, the terminal accepts 2x (0.5 to 2.5 mm²). No screwdriver needed — strip, insert, done. The main contact configuration is 18-8 (3 NO + 1 NC).
Operating Conditions & Performance
Coil pick-up voltage is 0.8 x rated (19.2 V for a 24 V coil), drop-out is below 18 V. Arcing time is 10 ms; DC operating time is 15-18 ms. Switching frequency varies by duty: 1000 ops/h for AC-1 (resistive), 750 ops/h for AC-2 and AC-3 (motor start/run), 250 ops/h for AC-4 (plugging/inching). Overload factor is 1.1.