SIRIUS 3RT2028-2XG40-0LA2 — DC Coil Contactor, Size S0
Rated for switching loads up to 10 A at 24 VDC, 2 A at 48 VDC and 60 VDC, 1 A at 110 VDC, 0.9 A at 125 VDC, and 0.3 A at 220 VDC.
Dimensions: 45 mm wide, 102 mm high, 107 mm deep — fits standard S0 footprint in a control panel.
Electrical Performance and Environment
DC dropout time is 30 to 50 ms; arcing time is 10 to 10 ms. Switching frequency: 750 operations per hour for AC-1, AC-2, AC-3, and AC-3e duty; 250 per hour for AC-4. Main contacts accept 2x (1 to 10 mm²) solid; auxiliary contacts accept 2x (0.5 to 2.5 mm²) solid or stranded. Initial pickup factor is 0.7; full-scale value is 1.25.