Part identity and deployment context
Motor-rated current and duty class
Rated 34 A at 480 V in AC-3 duty, this contactor handles motor switching up to that current — the rating that matters for sizing motor starters, not the AC-1 resistive figure. Mechanical switching frequency reaches 750 operations per hour under AC-3 and AC-2 duty, and 250 per hour under AC-4 — the heavier inching/plugging duty class.
Auxiliary contact capability
The built-in auxiliary switch (1 N/O + 1 N/C typical for the S0 frame) is rated for 10 A at 24 V, 2 A at 48/60 V, 1 A at 110 V, 0.9 A at 125 V, 0.3 A at 230 V, 3 A at 400 V, 0.6 A at 440 V, and 2 A at 500 V — covering control-circuit voltages from 24 VDC up to 500 VAC.