The coil accepts 20-33 VDC and draws 2 VA at both 50 and 60 Hz, meaning a standard 24 VDC control supply from a PLC or relay drives it directly. At 24 VDC rated value it switches 10 A; at 48 VDC, 2 A; at 110 VDC, 1 A; and at 220 VDC, 0.3 A — these are the DC-13 switching capacities for the auxiliary contacts, so the buyer should match the load voltage to the right column.
Switching duty and mechanical endurance
The contactor is rated for different switching frequencies depending on the utilization category. For AC-1 (resistive loads) it handles up to 1200 operations per hour; for AC-3 (squirrel-cage motors, starting and disconnecting running) it manages 1000 ops/h; for AC-4 (inching, plugging, reversing) it drops to 300 ops/h. The AC-3e rating also sits at 1000 ops/h. Arcing time runs 10-20 ms; operate time for both AC and DC coils is 30-55 ms, which is consistent for a Size S2 frame.