Skip to main content
Siemens 3RT2036-1AG60 — Contactors

Siemens 3RT2036-1AG60 SIRIUS Power Contactor, 52 A at 480 V

MPN3RT2036-1AG60
Active

Siemens SIRIUS S2 power contactor, 3RT2036-1AG60, screw-type coil terminals, 52 A at 480 V, 55 mm wide, snap-on 35 mm DIN rail mount.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

3RT2036-1AG60 — Identification
ParameterValue
Contactor frame sizeS2
3RT2036-1AG60 — Ratings & Performance
ParameterValue
Rated operational current, AC-12, max.10 A
Rated operational current, AC-4 @ 400 V41 A
Rated value @ 400 V3 A
Rated value @ 500 V2 A
Rated value @ 690 V1 A
Rated value @ 230 V10 hp
Rated value @ 24 V10 A
Rated value @ 60 V2 A
Rated value @ 110 V1 A
Rated value @ 220 V0.3 A
3RT2036-1AG60 — Control & Coil
ParameterValue
Control supply voltage typeAC
Rated value @ 50 Hz0.36
Rated value @ 50 Hz100 V
3RT2036-1AG60 — Contacts & Poles
ParameterValue
Main poles3
Main NO contacts3
Auxiliary contact reliability1 faulty switching per 100 million (17 V, 1 mA)
3RT2036-1AG60 — Protection & Coordination
ParameterValue
Short-circuit coordination type 1, fusegG: 160 A (690 V, 100 kA), aM: 80 A (690 V, 100 kA), BS88: 125 A (415 V, 80 kA)
Short-circuit coordination type 2, fusegG: 80A (690V,100kA), aM: 50A (690V,100kA), BS88: 63A (415V,80kA)
Aux. switch short-circuit protection, fusegG: 10 A (500 V, 1 kA)
3RT2036-1AG60 — Connection & Mounting
ParameterValue
Main circuit connectionscrew-type terminals
Aux. / control circuit connectionscrew-type terminals
Conductor cross-section, solid or stranded2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
Conductor cross-section, finely stranded w/ ferrule2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
Mounting methodscrew and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715
Side-by-side mountingYes
3RT2036-1AG60 — Durability
ParameterValue
Durability (operating cycles, typ.)10 000 000
Durability with aux. switch block (cycles, typ.)10 000 000
3RT2036-1AG60 — Environmental
ParameterValue
Operating temperature range-25 ... +60 °C
Storage temperature range-55 ... +80 °C
Installation altitude, max.2 000 m
3RT2036-1AG60 — Mechanical
ParameterValue
Width55 mm
Height114 mm
Depth130 mm
3RT2036-1AG60 — Specifications
ParameterValue
At AC10 ... 18 ms

Product details

The Siemens SIRIUS 3RT2036-1AG60 is a Size S2 power contactor rated for 52 A at 480 V (AC-3 duty), meaning it handles motor loads up to that current in a standard industrial panel.

The S2 frame is 55 mm wide, 114 mm tall, 130 mm deep, so it occupies a standard contactor footprint on the rail.

Switching performance and auxiliary contacts

Main contacts are rated 18 to 1. Arcing time runs 10 to 20 ms; make time is 10 to 18 ms at AC. Maximum switching frequency varies by duty: 1,000 ops/h at AC-1, 800 at AC-3, 600 at AC-2, 250 at AC-4. The auxiliary switch is included.

Coil ratings and auxiliary contact capacity

Auxiliary contact ratings: 10 A at 24 V, 2 A at 48 V and 60 V, 1 A at 110 V, 0.9 A at 125 V, 0.3 A at 220 V, 3 A at 400 V, 0.6 A at 440 V. The coil draws 0.36 A at 50 Hz and 0.39 A at 60 Hz (100 V rated value).

Storage and environmental limits

Frequently asked questions

What is 3RT2036-1AG60's listed depth?

The depth is 130 mm. Width is 55 mm and height is 114 mm.

MPN
3RT2036-1AG60