Rated 52 A at 480 V in AC-3 duty and 10 hp at 230 V, it handles the load of a medium conveyor or pump motor without breaking a sweat. Storage tolerance from -55 to +80 °C covers transit and warehouse extremes. The contactor's mechanical life is typical 10,000,000 operations — that's years of cycling in a production line before the contacts wear.
That 6 mm side gap is the one that catches people out; leave it or the arc chute doesn't vent properly. Dimensions: 114 mm high, 55 mm wide, 174 mm deep.
Arcing time runs 10 to 20 ms; the make time (at AC) is 10 to 18 ms. Those numbers matter for coordination with upstream breakers — the arc clears fast enough that a B-curve MCB won't nuisance trip on inrush. Switching frequency at AC-3 is 800 operations per hour maximum, at AC-4 it's 250 per hour. For heavy jogging or plugging duty, stay under the AC-4 limit or the contacts overheat. Coil draws 6 A at 24 V rated, 2 A at 48 V, 2 A at 60 V, 1 A at 110 V, 0.9 A at 125 V, 0.3 A at 220 V, and 3 A at 400 V. At 440 V it pulls 0.6 A. The coil operating range at 50 Hz is 0.36 times rated voltage; at 60 Hz it's 0.39. That means the contactor holds in during a brownout down to about 36% of nominal — useful in plants with weak utility feeds.