Skip to main content
Siemens 3RT2036-1AM20-0UA0 — Contactors

Siemens 3RT2036-1AM20-0UA0 SIRIUS Power Contactor, 52 A at 4

MPN3RT2036-1AM20-0UA0
Active

Siemens SIRIUS power contactor, size S2, 3RT2036-1AM20-0UA0, 52 A at 480 V, 208 V 50 Hz coil, screw-type terminals, screw and snap-on 35 mm DIN rail mounting.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3RT2036-1AM20-0UA0 — Identification
ParameterValue
Contactor frame sizeS2
3RT2036-1AM20-0UA0 — Ratings & Performance
ParameterValue
Rated operational current, AC-12, max.10 A
Rated operational current, AC-4 @ 400 V41 A
Rated value @ 400 V3 A
Rated value @ 500 V2 A
Rated value @ 690 V1 A
Rated value @ 230 V7.5 hp
Rated value @ 24 V10 A
Rated value @ 60 V2 A
Rated value @ 110 V1 A
Rated value @ 220 V0.3 A
3RT2036-1AM20-0UA0 — Control & Coil
ParameterValue
Control supply voltage typeAC
Rated value @ 50 Hz0.36
Rated value @ 50 Hz208 V
3RT2036-1AM20-0UA0 — Contacts & Poles
ParameterValue
Main poles3
Main NO contacts3
Auxiliary contact reliability1 faulty switching per 100 million (17 V, 1 mA)
3RT2036-1AM20-0UA0 — Protection & Coordination
ParameterValue
Short-circuit coordination type 1, fusegG: 160 A (690 V, 100 kA), aM: 80 A (690 V, 100 kA), BS88: 125 A (415 V, 80 kA)
Short-circuit coordination type 2, fusegG: 80A (690V,100kA), aM: 50A (690V,100kA), BS88: 63A (415V,80kA)
Aux. switch short-circuit protection, fusegG: 10 A (500 V, 1 kA)
3RT2036-1AM20-0UA0 — Connection & Mounting
ParameterValue
Main circuit connectionscrew-type terminals
Aux. / control circuit connectionscrew-type terminals
Conductor cross-section, solid or stranded2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
Conductor cross-section, finely stranded w/ ferrule2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
Mounting methodscrew and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715
Side-by-side mountingYes
3RT2036-1AM20-0UA0 — Durability
ParameterValue
Durability (operating cycles, typ.)10 000 000
Durability with aux. switch block (cycles, typ.)10 000 000
3RT2036-1AM20-0UA0 — Environmental
ParameterValue
Operating temperature range-25 ... +60 °C
Storage temperature range-55 ... +80 °C
Installation altitude, max.2 000 m
3RT2036-1AM20-0UA0 — Mechanical
ParameterValue
Width55 mm
Height114 mm
Depth130 mm
3RT2036-1AM20-0UA0 — Specifications
ParameterValue
At AC10 ... 18 ms

Product details

The Siemens SIRIUS 3RT2036-1AM20-0UA0 is a size S2 power contactor rated for 52 A at 480 V, with a 208 V 50 Hz coil. For resistive loads (AC-1), the switching frequency can go up to 1000 operations per hour; for AC-3 motor duty, 800 ops/h is the maximum.

Dimensions are 55 mm wide, 114 mm high, and 130 mm deep — a compact S2 footprint that leaves room for adjacent devices on the DIN rail. Terminals accept 2x (0.5 to 1.5 mm²) or 2x (0.75 to 2.5 mm²) solid or stranded wire. The screw-type coil terminals are standard for panel wiring — no special tooling needed. An auxiliary switch is included (18 to 1 configuration for main contacts), reducing the need for a separate add-on block in many simple motor starter circuits.

Coil draws 0.36 A at 50 Hz and 0.39 A at 60 Hz. Switching times: AC operate time 10 to 18 ms, arcing time 10 to 20 ms. Maximum switching frequency varies by duty: 1000 ops/h AC-1, 800 ops/h AC-3 and AC-3e, 600 ops/h AC-2, 250 ops/h AC-4. Auxiliary contact ratings: 10 A at 24 V, 2 A at 48 V and 60 V, 1 A at 110 V, 0.9 A at 125 V, 0.3 A at 220 V, 3 A at 400 V, 0.6 A at 440 V. Motor horsepower rating: 7.5 hp at 230 V.

Frequently asked questions

What are the key dimensions for panel layout?

Width is 55 mm, height 114 mm, depth 130 mm. Required clearances: 10 mm upwards, 10 mm forwards, 10 mm downwards, and 6 mm at the side.

What wire sizes does the contactor accept?

Terminals accept 2x (0.5 to 1.5 mm²) or 2x (0.75 to 2.5 mm²) solid or stranded wire, with screw-type connections.

What is the maximum switching frequency for motor duty?

For AC-3 motor duty, the maximum is 800 operations per hour. For AC-4 (inching/plugging), it is 250 ops/h.

MPN
3RT2036-1AM20-0UA0