Product Overview and Key Ratings
The coil is DC-operated with a rated value of 72 V, and the contactor features an extended operating range for reliable pick-up under varying control voltage conditions.
For panel layout planning, the dimensions are 55 mm width, 114 mm height, and 130 mm depth. The main contacts accept solid or stranded wire: 2x (0.5... 2.5 mm²).
Switching Capacity and Duty Ratings
The contactor's switching capacity is specified per voltage for DC-1 or similar resistive/inductive loads. At 24 V it switches 6 A; at 48 V and 60 V, 2 A; at 110 V, 1 A; at 125 V, 0.9 A; at 220 V, 0.3 A; at 400 V, 3 A; at 500 V, 2 A; at 690 V, 1 A. For motor duty at 230 V, it is rated 10 hp. The AC-4 maximum switching rate is 250 operations per hour. Mechanical endurance is typical 10,000,000 operations. Arcing time is 10... 20 ms.