It carries a 20-33 VDC coil and three main poles — the contact configuration is 18 to 1. The coil draws a 3 A inrush peak, then holds at 6 A at 24 V rated value, dropping to 2 A at 48 V, 2 A at 60 V, 1 A at 110 V, 0.9 A at 125 V, and 0.3 A at 220 V — so the holding power is low, but the inrush matters for the DC supply sizing. Switching rates vary by duty: up to 800 operations per hour in AC-1 (resistive), 700 in AC-3 (motor start/run), 400 in AC-2 (slip-ring motor), and 200 in AC-4 (plugging/inching). The AC-3e rate matches AC-3 at 700 1/h.
Dimensions: 114 mm high, 75 mm wide, 130 mm deep. Coil terminals are screw-type, accepting 2x (0.5 to 1.5 mm²) or 2x (0.75 to 2.5 mm²) solid or stranded wire. No auxiliary switch block is included as standard.