The coil accepts 20-33 V AC or DC, with an inrush peak of 3 A and holding draw of 2 VA at 50 or 60 Hz. Spring-type terminals on the coil reduce wiring time — no screw torque to verify, just strip and insert. Rated switching frequency varies by duty: 800 cycles/hour for AC-1 resistive loads, 700 for AC-3 motor starting, 400 for AC-2 slip-ring motors, and 200 for AC-4 plugging/reversing. That AC-3 figure (700 1/h) tells you it handles frequent conveyor starts without overheating the coil or arc chamber.
Integration Notes
Physical envelope: 114 mm high, 55 mm wide, 130 mm deep. The depth (130 mm) is the dimension that matters most when fitting into shallow enclosures — measure your backpanel clearance before committing. Side clearance of 6 mm and vertical clearance of 10 mm (up, down, forward) satisfy the manufacturer's ventilation and arc-flash spacing. The 60 °C ceiling covers most unventilated panel interiors, but derate switching frequency if ambient pushes above 40 °C — the thermal curve in the full datasheet governs that. Main contacts are 3-pole (3 normally open). An auxiliary switch block is included (yes per spec), so you have a feedback contact for PLC status without adding a separate side-mount.