Skip to main content
Siemens 3RT2038-3NB30-0CC0 — Contactors

Siemens 3RT2038-3NB30-0CC0 SIRIUS Power Contactor, 20-33 V C

MPN3RT2038-3NB30-0CC0
NRND

Siemens SIRIUS S2 power contactor, 3RT2038-3NB30-0CC0, 20-33 V coil, spring-type terminals, 55 mm wide, 130 mm deep, 114 mm tall.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3RT2038-3NB30-0CC0 — Identification
ParameterValue
Contactor frame sizeS2
3RT2038-3NB30-0CC0 — Ratings & Performance
ParameterValue
Rated operational current, AC-12, max.10 A
Rated operational current, AC-4 @ 400 V55 A
Rated value @ 400 V3 A
Rated value @ 500 V2 A
Rated value @ 690 V1 A
Rated value @ 230 V15 hp
Rated value @ 24 V10 A
Rated value @ 60 V2 A
Rated value @ 110 V1 A
Rated value @ 220 V0.3 A
3RT2038-3NB30-0CC0 — Control & Coil
ParameterValue
Control supply voltage typeAC/DC
Rated value @ 50 Hz2 VA
Rated value @ 50 Hz20 ... 33 V
3RT2038-3NB30-0CC0 — Contacts & Poles
ParameterValue
Main poles3
Main NO contacts3
Auxiliary contact reliability1 faulty switching per 100 million (17 V, 1 mA)
3RT2038-3NB30-0CC0 — Protection & Coordination
ParameterValue
Short-circuit coordination type 1, fusegG: 250 A (690 V, 100 kA), aM: 160 A (690 V, 100 kA), BS88: 200 A (415 V, 80 kA)
Short-circuit coordination type 2, fusegG: 160A (690V,100kA), aM: 80A (690V,100kA), BS88: 125A (415V,80kA)
Aux. switch short-circuit protection, fusegG: 10 A (500 V, 1 kA)
3RT2038-3NB30-0CC0 — Connection & Mounting
ParameterValue
Main circuit connectionscrew-type terminals
Aux. / control circuit connectionspring-loaded terminals
Conductor cross-section, solid or stranded2x (0.5 ... 2.5 mm²)
Conductor cross-section, finely stranded w/ ferrule2x (0.5 ... 1.5 mm²)
Mounting methodscrew and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715
Side-by-side mountingYes
3RT2038-3NB30-0CC0 — Durability
ParameterValue
Durability (operating cycles, typ.)10 000 000
Durability with aux. switch block (cycles, typ.)10 000 000
3RT2038-3NB30-0CC0 — Environmental
ParameterValue
Operating temperature range-25 ... +60 °C
Storage temperature range-55 ... +80 °C
Installation altitude, max.2 000 m
3RT2038-3NB30-0CC0 — Mechanical
ParameterValue
Width55 mm
Height114 mm
Depth130 mm
3RT2038-3NB30-0CC0 — Specifications
ParameterValue
At AC30 ... 55 ms

Product details

SIRIUS S2 power contactor — 3RT2038-3NB30-0CC0

The Siemens 3RT2038-3NB30-0CC0 is a SIRIUS S2-frame power contactor with a 20-33 V coil and spring-type terminals on the coil side. It snaps onto 35 mm DIN rail per DIN EN 60715 or screws directly to a backplate — the mounting position is flexible: ±180° rotation on a vertical surface, plus ±22.5° tilt forward/backward. That matters when you're shoehorning it into a crowded panel and the busbars don't line up.

This contactor is rated for different switching frequencies depending on the duty class. At AC-1 (resistive loads) it handles 700 operations per hour. AC-3 (standard motor starting) drops to 500 ops/h. AC-4 (plugging/reversing/inching) is the hard one — only 150 ops/h. If your application cycles a motor in reverse every 20 seconds, the AC-4 limit is the one that governs contact life, not the AC-3 number. The arcing time sits at 10-20 ms, which is typical for this frame size.

The 3RT2038-3NB30-0CC0 measures 55 mm wide, 130 mm deep, and 114 mm tall. That 6 mm side gap is tighter than some contactors — if you're packing multiple units side-by-side, verify the heat dissipation won't stack. The spring-type coil terminals are the same gauge range.

Frequently asked questions

Where can I buy 3RT2038-3NB30-0CC0 and how do I get a price?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time.

What are the key dimensions of this contactor?

The 3RT2038-3NB30-0CC0 is 55 mm wide, 130 mm deep, and 114 mm tall. Side clearance is 6 mm; top, bottom, and front clearance is 10 mm each.

What coil voltage does this contactor use?

The coil is rated for 20-33 V, with a pickup threshold of 0.8x the rated value. Inrush current peaks at 3 A; holding power is 2 VA at both 50 Hz and 60 Hz.

What switching frequency can this contactor handle?

It depends on the duty class: 700 ops/h for AC-1 resistive loads, 500 ops/h for AC-3 motor starting, and 150 ops/h for AC-4 plugging/reversing duty.

MPN
3RT2038-3NB30-0CC0