SIRIUS S3 contactor, 110 VDC coil, spring-terminal
The coil draws a 1.5 A inrush peak and holds at the 110 VDC rated value.
Auxiliary contact switching capability
The integrated auxiliary switch is rated across DC voltage levels: 6 A at 24 V, 2 A at 48 V and 60 V, 1 A at 110 V, 0.9 A at 125 V, 0.3 A at 220 V, 3 A at 400 V, 2 A at 500 V, and 1 A at 690 V. These ratings define the DC-13 switching curve for the auxiliary contacts — useful when interposing to a PLC input or pilot relay. The arcing time spans 10 to 20 ms; the DC operate time is 38 to 57 ms.
The contactor is rated for 10 million typical mechanical operations. The AC-4 maximum switching rate is 300 operations per hour.