Skip to main content
Siemens 3RT2046-3XJ44-0LA2 — Contactors

Siemens 3RT2046-3XJ44-0LA2 SIRIUS Contactor, 70 mm, 200 mm d

MPN3RT2046-3XJ44-0LA2
Active

Siemens SIRIUS contactor, size S3, 3RT2046-3XJ44-0LA2, 70 mm width, 200 mm depth, spring-type terminals, extended operating range, DC coil 72 V.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3RT2046-3XJ44-0LA2 — Identification
ParameterValue
Contactor frame sizeS3
3RT2046-3XJ44-0LA2 — Ratings & Performance
ParameterValue
Rated operational current, AC-12, max.10 A
Rated operational current, AC-4 @ 400 V80 A
Rated value @ 400 V3 A
Rated value @ 500 V2 A
Rated value @ 690 V1 A
Rated value @ 230 V20 hp
Rated value @ 24 V6 A
Rated value @ 60 V2 A
Rated value @ 110 V1 A
Rated value @ 220 V0.3 A
3RT2046-3XJ44-0LA2 — Control & Coil
ParameterValue
Control supply voltage typeDC
3RT2046-3XJ44-0LA2 — Contacts & Poles
ParameterValue
Main poles3
Main NO contacts3
3RT2046-3XJ44-0LA2 — Protection & Coordination
ParameterValue
Short-circuit coordination type 1, fusegG: 250 A (690 V, 100 kA), aM: 160 A (690 V, 100 kA), BS88: 200 A (415 V, 80 kA)
Short-circuit coordination type 2, fusegG: 160 A (690 V, 100 kA), aM: 100 A (690 V, 100 kA), BS88: 125 A (415 V, 80 kA)
Aux. switch short-circuit protection, fusegG: 10 A (500 V, 1 kA)
3RT2046-3XJ44-0LA2 — Connection & Mounting
ParameterValue
Main circuit connectionscrew-type terminals
Aux. / control circuit connectionspring-loaded terminals
Conductor cross-section, solid or stranded2x (0.5 ... 2.5 mm²)
Conductor cross-section, finely stranded w/ ferrule2x (0.5 ... 1.5 mm²)
Mounting methodscrew and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 60715
Side-by-side mountingYes
3RT2046-3XJ44-0LA2 — Durability
ParameterValue
Durability (operating cycles, typ.)10 000 000
Durability with aux. switch block (cycles, typ.)10 000 000
3RT2046-3XJ44-0LA2 — Environmental
ParameterValue
Operating temperature range-40 ... +70 °C
Storage temperature range-55 ... +80 °C
Installation altitude, max.2 000 m
3RT2046-3XJ44-0LA2 — Mechanical
ParameterValue
Width70 mm
Height140 mm
Depth200 mm

Product details

The Siemens 3RT2046-3XJ44-0LA2 is a SIRIUS contactor in size S3, designed with an extended operating range and a DC coil rated at 72 V. It uses spring-type terminals for the magnet coil, and the main contacts are rated for switching at 480 V up to 96 A. The contactor mounts via screw or snap-on onto a 35 mm DIN rail per DIN EN 60715, with a width of 70 mm and a depth of 200 mm — dimensions that fit standard panel layouts.

The mounting position allows ±180° rotation on a vertical surface, plus ±22.5° tilt forward/backward on a vertical surface. Clearances: 10 mm upwards, 20 mm forwards, 10 mm downwards, 10 mm at the side. The 70 mm width and 200 mm depth fit standard DIN-rail enclosures without crowding adjacent devices.

Frequently asked questions

How do I get current pricing and availability for 3RT2046-3XJ44-0LA2?

Pricing and availability are confirmed at quote time against an RFQ through independent distribution. Submit an RFQ for a current quote.

What is 3RT2046-3XJ44-0LA2's listed depth and width?

The depth is 200 mm and the width is 70 mm.

Will 3RT2046-3XJ44-0LA2 drop into a panel specified around 3RT1054-2AP36 without rewiring?

The 3RT2046-3XJ44-0LA2 is a size S3 contactor with a 70 mm width and 200 mm depth, while the 3RT1054-2AP36 is a different frame size. Panel fit depends on the existing mounting rail and clearance dimensions; verify the physical envelope before substitution.

What compliance documentation does this brand provide for 3RT2046-3XJ44-0LA2?

The evidence does not list specific compliance documents (RoHS, REACH, UL, IEC) for this order code. Contact the supplier at quote time for the documentation package.

MPN
3RT2046-3XJ44-0LA2