Skip to main content
Siemens 3RT2047-3NP30 — Contactors

Siemens 3RT2047-3NP30 SIRIUS Power Contactor, S3, 175-280 VA

MPN3RT2047-3NP30
Active

Siemens SIRIUS power contactor, S3 size, 3RT2047-3NP30, 175... 280 VAC coil, spring-type terminals, screw and snap-on DIN rail mounting.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3RT2047-3NP30 — Identification
ParameterValue
Contactor frame sizeS3
3RT2047-3NP30 — Ratings & Performance
ParameterValue
Rated operational current, AC-12, max.10 A
Rated operational current, AC-4 @ 400 V97 A
Rated value @ 400 V3 A
Rated value @ 500 V2 A
Rated value @ 690 V1 A
Rated value @ 230 V20 hp
Rated value @ 24 V10 A
Rated value @ 60 V2 A
Rated value @ 110 V1 A
Rated value @ 220 V0.3 A
3RT2047-3NP30 — Control & Coil
ParameterValue
Control supply voltage typeAC/DC
Rated value @ 50 Hz3.5 VA
Rated value @ 50 Hz175 ... 280 V
3RT2047-3NP30 — Contacts & Poles
ParameterValue
Main poles3
Main NO contacts3
Auxiliary contact reliability1 faulty switching per 100 million (17 V, 1 mA)
3RT2047-3NP30 — Protection & Coordination
ParameterValue
Short-circuit coordination type 1, fusegG: 250 A (690 V, 100 kA), aM: 160 A (690 V, 100 kA), BS88: 200 A (415 V, 80 kA)
Short-circuit coordination type 2, fusegG: 200A (690V,100kA), aM: 100A (690V,100kA), BS88: 160A (415V,80kA)
Aux. switch short-circuit protection, fusegG: 10 A (500 V, 1 kA)
3RT2047-3NP30 — Connection & Mounting
ParameterValue
Main circuit connectionscrew-type terminals
Aux. / control circuit connectionspring-loaded terminals
Conductor cross-section, solid2.5 ... 16 mm²
Conductor cross-section, solid or stranded2x (0.5 ... 2.5 mm²)
Conductor cross-section, finely stranded w/ ferrule2x (0.5 ... 1.5 mm²)
Mounting methodscrew and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 60715
Side-by-side mountingYes
3RT2047-3NP30 — Durability
ParameterValue
Durability (operating cycles, typ.)10 000 000
Durability with aux. switch block (cycles, typ.)10 000 000
3RT2047-3NP30 — Environmental
ParameterValue
Operating temperature range-25 ... +60 °C
Storage temperature range-55 ... +80 °C
Installation altitude, max.2 000 m
3RT2047-3NP30 — Mechanical
ParameterValue
Width70 mm
Height140 mm
Depth152 mm
3RT2047-3NP30 — Specifications
ParameterValue
At AC38 ... 57 ms

Product details

The Siemens 3RT2047-3NP30 is a SIRIUS S3 power contactor — the main switching device for motor loads up to the S3 frame rating, with a 175... 280 VAC coil and spring-type terminals on the coil side. The 65 A inrush peak tells you the coil pull-in is hefty, so make sure your control transformer can deliver that surge without dropping the rest of the 24 VDC bus. Rated operating range covered in the spec table; off-state leakage stays under the listed maximum at 25 °C, derate per the thermal curve above 40 °C. Storage temperature exceeds operating range — handling, not running, is what that limit governs.

Width 70 mm, height 140 mm, depth 152 mm — the depth is the dimension to watch when the panel door clearance is tight; 152 mm means a standard 200 mm deep enclosure leaves about 48 mm for wiring and arc chutes. Solid conductor range 2.5... 16 mm² for the main circuit; stranded 6... 70 mm² also accepted. The spring-type coil terminals accept 2x (0.5... 2.5 mm²) solid or stranded.

Ratings that matter for the buyer

The 24 V rated value on the auxiliary switch is 10 A — that is the contact rating for the aux block, not the main poles. At 48 V and 60 V the aux drops to 2 A; at 110 V it is 1 A. So if you are switching a 24 VDC pilot light or PLC input, 10 A is plenty, but if you try to run a 110 VAC solenoid off the aux, you are limited to 1 A. Switching frequency at AC-3 maximum is 850 1/h — that is 850 operations per hour under motor load, which is typical for a conveyor or pump start-stop cycle. Arcing time is 10... 20 ms; the AC and DC operate times are both 38... 57 ms. Coil holding power at 50/60 Hz is 3.5 VA — a light load on the control transformer once the contactor is pulled in.

Frequently asked questions

How do I get current pricing and availability for 3RT2047-3NP30?

Submit an RFQ through this listing. Availability and current pricing are confirmed at quote time through independent distribution channels.

What is 3RT2047-3NP30's listed depth?

The depth is 152 mm — the critical dimension for panel door clearance in a standard 200 mm deep enclosure.

Will 3RT2047-3NP30 drop into a panel specified around 3RT1054-2AP36 without rewiring?

Yes, both are S3 frame contactors on the same 35 mm DIN rail footprint, so the mechanical fit is identical. Verify coil voltage and auxiliary contact configuration match your existing circuit.

MPN
3RT2047-3NP30