Skip to main content
Siemens 3RT2316-2AF00-1AA0-ZX95 — Contactors

Siemens 3RT2316-2AF00-1AA0-ZX95 SIRIUS Contactor

MPN3RT2316-2AF00-1AA0-ZX95

Siemens SIRIUS 3RT2316-2AF00-1AA0-ZX95 contactor, size S00, 4 NO main contacts, 4 kW at 400 V AC-3, 110 V 50/60 Hz coil, spring-loaded terminals, screw and snap-on DIN rail mount.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3RT2316-2AF00-1AA0-ZX95 — Identification
ParameterValue
Contactor frame sizeS00
3RT2316-2AF00-1AA0-ZX95 — Ratings & Performance
ParameterValue
Rated operational current, AC-4 @ 400 V4 kW
Rated value @ 400 V4 kW
3RT2316-2AF00-1AA0-ZX95 — Control & Coil
ParameterValue
Control supply voltage typeAC
Rated value @ 50 Hz0.8 ... 1.1
Rated value @ 50 Hz110 V
3RT2316-2AF00-1AA0-ZX95 — Contacts & Poles
ParameterValue
Main poles4
Main NO contacts4
3RT2316-2AF00-1AA0-ZX95 — Protection & Coordination
ParameterValue
Short-circuit coordination type 1, fusegG: 35 A (690 V, 100 kA)
Short-circuit coordination type 2, fusegG: 20 A (690 V, 100 kA)
Aux. switch short-circuit protection, fusegG: 10 A (690 V, 1 kA)
3RT2316-2AF00-1AA0-ZX95 — Connection & Mounting
ParameterValue
Main circuit connectionspring-loaded terminals
Conductor cross-section, finely stranded w/ ferrule2x (0.5 ... 2.5 mm²)
3RT2316-2AF00-1AA0-ZX95 — Mechanical
ParameterValue
Width45 mm
Depth73 mm
3RT2316-2AF00-1AA0-ZX95 — Specifications
ParameterValue
At AC3.5 ... 14 ms

Product details

The 3RT2316-2AF00-1AA0-ZX95: The front face carries IP20 finger-safe protection, meaning the bus bars and terminations are touch-safe behind the enclosure door.

DIN rail snap-on with side-by-side stacking

The S00 frame is the smallest SIRIUS contactor body — useful when panel fill factor is tight. Upwards clearance of 10 mm and forwards clearance of 10 mm are the minimum free air around the arc chutes; a panel layout that respects those keeps the switching frequency at the rated 1 000 cycles per hour at AC-1.

Coordination and mirror contact for safety circuits

The contactor supports Type 1 coordination with a 35 A gG fuse (690 V, 100 kA) and Type 2 coordination with a 20 A gG fuse — the fuse selection determines whether the contactor survives a short-circuit fault or needs replacement. A mirror contact per IEC 60947-4-1 is available when paired with the 3RH29 auxiliary contact block, which is the standard requirement for safety-related isolation in a SIL/PL-rated circuit. The auxiliary switch block is ordered separately — the contactor body carries the main poles only.

Sourced to order against the BOM quantity through independent distribution.

Frequently asked questions

What fuse rating is needed for Type 2 coordination?

For Type 2 coordination per IEC 60947-4-1, use a gG fuse rated 20 A at 690 V, 100 kA. For Type 1 coordination, a 35 A gG fuse at the same voltage and breaking capacity is specified.

Does 3RT2316-2AF00-1AA0-ZX95 include auxiliary contacts?

No — the contactor body carries only the four main NO contacts. An auxiliary switch block (e.g. 3RH29 series) must be ordered separately to add NO/NC auxiliary poles.

MPN
3RT2316-2AF00-1AA0-ZX95