Skip to main content
Siemens 3RT2316-2BW40 — Contactors

Siemens 3RT2316-2BW40 SIRIUS Contactor, 4 kW AC-3, Spring Te

MPN3RT2316-2BW40
Active

Siemens SIRIUS 3RT2316-2BW40, size S00 contactor, 4 kW / 9 A AC-3 at 400 V, spring-loaded terminals, 45 mm width, current production.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3RT2316-2BW40 — Identification
ParameterValue
Contactor frame sizeS00
3RT2316-2BW40 — Ratings & Performance
ParameterValue
Rated operational current, AC-4 @ 400 V4 kW
Rated value @ 400 V9 A
3RT2316-2BW40 — Control & Coil
ParameterValue
Control supply voltage typeDC
3RT2316-2BW40 — Contacts & Poles
ParameterValue
Main poles4
Main NO contacts4
3RT2316-2BW40 — Protection & Coordination
ParameterValue
Short-circuit coordination type 1, fusegG: 35 A (690 V, 100 kA)
Short-circuit coordination type 2, fusegG: 20 A (690 V, 100 kA)
Aux. switch short-circuit protection, fusegG: 10 A (690 V, 1 kA)
3RT2316-2BW40 — Connection & Mounting
ParameterValue
Main circuit connectionspring-loaded terminals
Aux. / control circuit connectionspring-loaded terminals
Conductor cross-section, solid2x (0.5 ... 2.5 mm²)
Conductor cross-section, solid or stranded2x (0,5 ... 4 mm²)
Conductor cross-section, finely stranded w/ ferrule2x (0.5 ... 2.5 mm²)
Mounting methodscrew and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715
Side-by-side mountingYes
3RT2316-2BW40 — Durability
ParameterValue
Durability (operating cycles, typ.)30 000 000
Durability with aux. switch block (cycles, typ.)10 000 000
3RT2316-2BW40 — Environmental
ParameterValue
Operating temperature range-25 ... +60 °C
Storage temperature range-55 ... +80 °C
Installation altitude, max.2 000 m
3RT2316-2BW40 — Mechanical
ParameterValue
Width45 mm
Height70 mm
Depth73 mm

Product details

SIRIUS 3RT2316-2BW40 — S00 Contactor with Spring-Loaded Terminals

The Siemens 3RT2316-2BW40 is a SIRIUS-branded contactor in the compact S00 frame size, rated for 4 kW motor switching in AC-3 duty at 400 V (9 A rated operational current). The spring-loaded terminals on the main current circuit accept solid conductors 2x (0.5... 2.5 mm²) or stranded 0.5... 4 mm², making it a tool-less wiring choice for panel builders who want to reduce termination time on DIN-rail assemblies.

For AC-4 duty (plugging, inching, reversing) at 400 V, the rating holds at 4 kW, meaning the contactor is sized for frequent jogging applications without derating the motor power. The auxiliary switch is built in, with contact ratings of 20... 12 for the auxiliary contacts — this covers the typical 24 V DC or 120 V AC control signals used in PLC-driven panels. The coil is DC-operated at 48 V rated value, with a pickup time of 7... 13 ms and arcing time of 10... 15 ms, which is fast enough for most sequencing applications but should be verified against the PLC scan cycle if the contactor is used in a safety-related interlock path. Power dissipation is 4.4 W at AC in the hot operating state — a useful number for enclosure thermal calculations when multiple contactors are ganged side-by-side.

The 45 mm width and 70 mm height (73 mm depth) fit the S00 footprint, leaving clearance requirements of 10 mm upwards, 10 mm forwards, 10 mm downwards, and 6 mm at the side. Side-by-side mounting is permitted, which is typical for multi-contactor motor starter assemblies in a panel.

The contactor carries a RoHS compliance date of 10/01/2009, confirming it meets the EU Restriction of Hazardous Substances directive.

Frequently asked questions

What is the AC-3 motor rating of 3RT2316-2BW40?

The contactor is rated 4 kW at 400 V AC-3 for motor switching, with a rated operational current of 9 A at 400 V. This covers standard squirrel-cage induction motors up to that load.

What terminal type does 3RT2316-2BW40 use?

The main current circuit uses spring-loaded terminals (spring-type terminals on the magnet coil as well). They accept solid conductors 2x (0.5... 2.5 mm²) and stranded 0.5... 4 mm², allowing tool-less wiring.

Where can I buy 3RT2316-2BW40 and what is the lead time?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm lead-time and price commitment.

Will 3RT2316-2BW40 drop into a panel specified for 3RT2015-2BF42?

Both are S00 frame size contactors on 35 mm DIN rail, so the physical footprint and mounting are identical. The 3RT2316-2BW40 uses spring-loaded terminals, while the 3RT2015-2BF42 may use screw terminals — verify the wiring method matches your panel's terminal blocks. The coil voltage and auxiliary contact configuration should be checked against the existing BOM.

What compliance documentation does Siemens provide for 3RT2316-2BW40?

RoHS compliance is confirmed with a substance prohibition date of 10/01/2009. The contactor also carries a rated impulse withstand voltage of 6 kV for both main and auxiliary circuits, indicating IEC 60947 compliance. Full declarations and certificates are typically available from Siemens Industry Online Support.

MPN
3RT2316-2BW40