Skip to main content
Siemens 3RT2317-2AP60 — Contactors

Siemens 3RT2317-2AP60 SIRIUS Contactor, 5.5 kW AC-3 at 400 V

MPN3RT2317-2AP60
Active

Siemens SIRIUS contactor, size S00, 3RT2317-2AP60, 5.5 kW AC-3 at 400 V, spring-loaded terminals, screw and snap-on 35 mm DIN rail.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3RT2317-2AP60 — Identification
ParameterValue
Contactor frame sizeS00
3RT2317-2AP60 — Ratings & Performance
ParameterValue
Rated operational current, AC-4 @ 400 V4 kW
Rated value @ 400 V12 A
3RT2317-2AP60 — Control & Coil
ParameterValue
Control supply voltage typeAC
Rated value @ 50 Hz0.24
Rated value @ 50 Hz220 V
3RT2317-2AP60 — Contacts & Poles
ParameterValue
Main poles4
Main NO contacts4
3RT2317-2AP60 — Protection & Coordination
ParameterValue
Short-circuit coordination type 1, fusegG: 35 A (690 V, 100 kA)
Short-circuit coordination type 2, fusegG: 20 A (690 V, 100 kA)
Aux. switch short-circuit protection, fusegG: 10 A (690 V, 1 kA)
3RT2317-2AP60 — Connection & Mounting
ParameterValue
Main circuit connectionspring-loaded terminals
Aux. / control circuit connectionspring-loaded terminals
Conductor cross-section, solid2x (0.5 ... 2.5 mm²)
Conductor cross-section, solid or stranded2x (0,5 ... 4 mm²)
Conductor cross-section, finely stranded w/ ferrule2x (0.5 ... 2.5 mm²)
Mounting methodscrew and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715
Side-by-side mountingYes
3RT2317-2AP60 — Durability
ParameterValue
Durability (operating cycles, typ.)30 000 000
Durability with aux. switch block (cycles, typ.)10 000 000
3RT2317-2AP60 — Environmental
ParameterValue
Operating temperature range-25 ... +60 °C
Storage temperature range-55 ... +80 °C
Installation altitude, max.2 000 m
3RT2317-2AP60 — Mechanical
ParameterValue
Width45 mm
Height70 mm
Depth73 mm
3RT2317-2AP60 — Specifications
ParameterValue
At AC7 ... 13 ms

Product details

The Siemens SIRIUS 3RT2317-2AP60 is a size S00 contactor rated for 5.5 kW at 400 V in AC-3 duty — the standard motor-switching category for squirrel-cage induction motors. That 5.5 kW rating at 400 V tells you the motor load it can handle under normal starting and running conditions. The 12 A rated operational current at 400 V is the thermal limit for the main poles in that duty.

Both the main current circuit and the magnet coil use spring-loaded (spring-type) terminals. The main contacts accept solid conductors 2x (0.5 to 2.5 mm²) or stranded 0.5 to 4 mm². Auxiliary contacts use the same spring-cage style, sized for 2x (0.5 to 2.5 mm²) solid. No screw torque to verify — just strip and insert.

Relative humidity minimum 10%. RoHS compliance date is October 1, 2009, covering the EU RoHS substance restrictions.

MPN
3RT2317-2AP60