S0 frame, 24 V AC coil, screw terminals
The 3RT2325-1AP60: The coil draws 0.25 A at 50 Hz and 0.28 A at 60 Hz — factor that into the control transformer sizing for a multi-contactor panel. Rated for 10 million mechanical operations typical, so it holds up in high-cycle applications like conveyor sortation or packaging machinery where the contactor cycles every few seconds.
Auxiliary contact block and wiring capacity
The contactor accepts up to two attachable auxiliary switch blocks. The 24 V DC rating is 10 A; at 125 V DC it drops to 0.9 A — a typical derating curve for DC switching where arc extinction is harder.
DIN rail mounting with position flexibility
The 97 mm depth means it projects about 4 inches from the DIN rail — check the enclosure depth against the door clearance if mounted near a hinge.