Specifications

3RT2326-1AP60 — Identification
ParameterValue
Contactor frame sizeS0
3RT2326-1AP60 — Ratings & Performance
ParameterValue
Rated operational current, AC-12, max.10 A
Rated operational current, AC-4 @ 400 V7.5 kW
Rated value @ 400 V3 A
Rated value @ 500 V2 A
Rated value @ 690 V1 A
Rated value @ 230 V10 A
Rated value @ 24 V10 A
Rated value @ 60 V6 A
Rated value @ 110 V1 A
Rated value @ 220 V0.3 A
3RT2326-1AP60 — Control & Coil
ParameterValue
Control supply voltage typeAC
Rated value @ 50 Hz0.25
Rated value @ 50 Hz220 V
3RT2326-1AP60 — Contacts & Poles
ParameterValue
Main poles4
Main NO contacts4
Auxiliary contact reliability1 faulty switching per 100 million (17 V, 1 mA)
3RT2326-1AP60 — Protection & Coordination
ParameterValue
Short-circuit coordination type 1, fusegG: 63 A (690 V, 100 kA)
Short-circuit coordination type 2, fusegG: 20 A (690 V, 100 kA)
Aux. switch short-circuit protection, fusegG: 10 A (690 V, 1 kA)
3RT2326-1AP60 — Connection & Mounting
ParameterValue
Main circuit connectionscrew-type terminals
Aux. / control circuit connectionscrew-type terminals
Conductor cross-section, solid2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
Conductor cross-section, solid or stranded2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
Conductor cross-section, finely stranded w/ ferrule2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
Mounting methodscrew and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715
Side-by-side mountingYes
3RT2326-1AP60 — Durability
ParameterValue
Durability (operating cycles, typ.)10 000 000
Durability with aux. switch block (cycles, typ.)10 000 000
3RT2326-1AP60 — Environmental
ParameterValue
Operating temperature range-25 ... +60 °C
Storage temperature range-55 ... +80 °C
Installation altitude, max.2 000 m
3RT2326-1AP60 — Mechanical
ParameterValue
Width60 mm
Height85 mm
Depth97 mm
3RT2326-1AP60 — Specifications
ParameterValue
At AC4 ... 16 ms

Product details

The 3RT2326-1AP60: Rated for ambient operation from -25 to +60 °C and storage from -55 to +80 °C, it suits typical industrial panel environments. Mounting options include screw fixing or snap-on onto 35 mm DIN rail (EN 60715), with ±180° rotation and ±22.5° tilt for tight layouts.

Main terminals accept 1–10 mm² stranded conductors, while the coil terminals take 2x (0.5–1.5 mm²) or 2x (0.75–2.5 mm²) solid wire per clamp. This capacity covers most motor-circuit wiring without terminal reducers.

Frequently asked questions

What is the depth of this contactor?

The depth is 97 mm.

What solid conductor sizes can the coil terminals accept?

Each coil terminal accepts 2x (0.5 to 1.5 mm²) or 2x (0.75 to 2.5 mm²) solid wire.