SIRIUS S0 Contactor, 24 VDC Coil
Auxiliary Contact Ratings Across DC Voltages
The built-in auxiliary switch carries DC ratings that vary significantly by voltage: 10 A at 24 V and 230 V, 6 A at 60 V, 3 A at 400 V, 2 A at 48 V and 500 V, 1 A at 110 V and 690 V, 0.9 A at 125 V, 0.3 A at 220 V, and 0.1 A at 600 V. This spread reflects the arc-extinction limits at higher DC voltages — the 0.1 A at 600 V rating is the practical ceiling for this switch block.
The S0 frame measures 85 mm high by 60 mm wide by 107 mm deep.
Terminal Specifications
Main contact terminals accept solid or stranded wire: 1 to 10 mm² stranded, or 2x (0.5 to 1.5 mm²) and 2x (0.75 to 2.5 mm²) solid. The coil uses screw-type terminals. Mechanical life is typically 10,000,000 operations. Arcing time is 10 ms.