The coil accepts 83... 155 V AC/DC, which covers common 110 V and 120 V control circuits without needing a separate rectifier or transformer tap. Pickup is guaranteed at 80 % of rated voltage; drop-out occurs at 110 % — so it holds in during brownouts down to roughly 66 V on a 83 V setting.
Auxiliary Contact Ratings and Wiring
The 3RT2336-1NF30 ships with one NO and one NC auxiliary contact (2 attachable total). At 400 V AC the auxiliary switches 3 A. This covers feedback to a PLC input or interlocking a safety circuit without an external relay. Terminals accept 2x 0.5... 1.5 mm² solid or 2x 0.75... 2.5 mm² stranded — enough for standard control wiring. The coil terminals are screw-type, so a wireman can terminate with a standard Pozidriv #2 without special tooling.
Mounting Clearances and Position Flexibility
Side clearance is 6 mm; forward and upward clearance is 10 mm; downward clearance is also 10 mm.