Side-by-side mounting is permitted with 6 mm gap between units — no forced spacing for thermal reasons, but that gap keeps the screwdriver accessible for the screw-type terminals. Dimensions are 45 mm wide, 57.5 mm high, 73 mm deep — a compact footprint for the S00 frame size. The screw-type terminals accept solid or stranded wire: 2x (0.5 to 1.5 mm²), 2x (0.75 to 2.5 mm²), or 2x 4 mm². That covers most control-circuit wiring up to 4 mm² without needing ring lugs.
Auxiliary contact ratings and switching performance
The integrated auxiliary switch is rated for 10 A at 24 V DC and 10 A at 230 V AC, with lower ratings at intermediate voltages (2 A at 48 V DC, 2 A at 60 V DC, 1 A at 110 V DC, 0.3 A at 220 V DC, 3 A at 400 V AC, 0.1 A at 600 V AC). These are the make/break capacities for the auxiliary contacts — useful for signaling to a PLC or driving a small relay.
Environmental range and operating limits
The coil is rated at 200 V at 50 Hz and 200 to 220 V at 60 Hz — but this unit uses a 24 V DC coil, so those AC coil ratings apply to a different variant; the 24 V DC coil pull-in and hold characteristics follow the standard SIRIUS curve for the S00 frame.