SIRIUS S00 contactor, 400 V 50 Hz coil — panel-fit and ratings
This contactor carries a built-in auxiliary switch. The voltage-specific current ratings tell you what the auxiliary contacts can safely break at different DC voltage levels. At 24 V it switches 10 A; at 48 V and 60 V it handles 2 A; at 110 V it drops to 1 A; at 220 V it's 0.3 A; at 600 V it's 0.1 A. For AC loads, at 230 V it switches 10 A, and at 400 V it switches 3 A. These figures govern the auxiliary circuit — a PLC input or a holding relay — not the main power path.
Mounting flexibility and clearance
Side-by-side mounting is supported with a 6 mm lateral clearance. No vertical clearance needed above, below, forward, or backward in free-air mounting — useful when packing multiple contactors into a tight sub-panel.