SIRIUS 3RT2517-1AP00 — Size S00 Contactor with 24 V AC Coil
It mounts via screw and snap-on onto 35 mm DIN rail per DIN EN 50022, fitting into a 45 mm wide slot with a 57.5 mm height and 73 mm depth — a footprint that leaves room for adjacent devices in a crowded enclosure. The magnet coil is rated 230 V at 50 Hz and 230 V at 60 Hz, drawing 0.25 A at both frequencies. Screw-type terminals on the coil accept solid or stranded conductors: 2x (0.5 to 1.5 mm²), 2x (0.75 to 2.5 mm²), or 2x 4 mm² — a practical range for panel wiring with standard ferrule sizes.
Ratings and Switching Capacity
In AC-1 duty (resistive loads), the main contacts carry 10 A at 24 V and 10 A at 230 V — the same 10 A rating across both common control voltages. At 400 V the AC-1 rating drops to 3 A, and at 600 V to 0.1 A, reflecting the arc extinction limits in the S00 frame. For DC switching, the contactor is rated 10 A at 24 V DC, 2 A at 48 V and 60 V DC, and 0.3 A at 220 V DC — figures that govern solenoid and small DC motor applications. Mechanical endurance is typical 30 million operations, with a maximum switching frequency of 1,000 cycles per hour under AC-1 load and 10,000 cycles per hour for DC operation.
No additional spacing is needed upwards, forwards, backwards, or downwards — all rated at 0 mm — so the contactor can be stacked flush in a DIN-rail row.