That's a standard panel footprint — 75 mm wide, 114 mm tall, 130 mm deep — so it drops into most existing layouts without re-drilling the backplate. Coil terminals are screw-type, and the contactor carries an auxiliary switch block. The main contacts are rated 10 A at 24 V, 6 A at 230 V, and 3 A at 400 V — figures that tell you this is a control-duty contactor, not a power-feed device.
Clearance and Wiring
Clearance requirements are tight: 0 mm forward and backward, 50 mm upward and downward, 10 mm at the sides. That means you can pack contactors side-by-side with no gap front-to-back, but you need breathing room above and below for wiring and heat dissipation. Solid wire sizes accepted are 2x (0.5 to 1.5 mm²) and 2x (0.75 to 2.5 mm²) — standard control wiring, nothing exotic. Operating time at AC is 10 to 18 ms, arcing time 10 to 20 ms. That's fast enough for most sequencing applications, but if you're coordinating with semiconductor outputs or fast PLC cycles, account for the arcing window in your timing budget.