SIRIUS Size S2 Contactor — 3RT2536-1NF30
Its 83-155 VAC coil covers common European and North American control voltages. The contactor carries an auxiliary switch as standard and is rated for a mechanical life of 10,000,000 cycles typical. Clearance distances are 50 mm upward/downward, 10 mm sideways, and 0 mm forward/backward — plan your DIN rail layout accordingly.
Switching Capacity & Coil Specs
Rated switching capacity varies by voltage: 10 A at 24 VAC and 230 VAC, 3 A at 400 VAC, 2 A at 48/60 VAC, 1 A at 110 VAC, 0.9 A at 125 VAC, 0.3 A at 220 VAC, and 0.4 A at 440 VAC. The inrush current peak is 12 A. The maximum AC-1 switching rate is 350 operations per hour. Coil terminals are screw-type, accepting 2x (0.5-1.5 mm²) solid or 2x (0.75-2.5 mm²) stranded conductors.
Environmental & Lifecycle
Dimensions: 130 mm deep × 114 mm high × 75 mm wide. The Size S2 frame fits standard 35 mm DIN rail; snap-on mounting allows quick install without tools.