Skip to main content
Siemens 3RT2625-1AK65 — Contactors

Siemens 3RT2625-1AK65 SIRIUS Capacitor Contactor

MPN3RT2625-1AK65
Active

Siemens SIRIUS 3RT2625-1AK65 capacitor contactor, S0 frame size, 110 VAC 50 Hz coil, screw-type terminals, 45 mm width, 135 mm height, 155 mm depth, DIN rail mount.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3RT2625-1AK65 — Identification
ParameterValue
Contactor frame sizeS0
3RT2625-1AK65 — Control & Coil
ParameterValue
Control supply voltage typeAC
Rated value @ 50 Hz0.8 ... 1.1
Rated value @ 50 Hz110 ... 110 V
3RT2625-1AK65 — Contacts & Poles
ParameterValue
Main poles3
Main NO contacts3
Auxiliary contact reliability0.00000001
3RT2625-1AK65 — Protection & Coordination
ParameterValue
Aux. switch short-circuit protection, fusegG: 10 A (500 V, 1 kA)
3RT2625-1AK65 — Connection & Mounting
ParameterValue
Main circuit connectionscrew-type terminals
Aux. / control circuit connectionscrew-type terminals
Conductor cross-section, solid2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), 2x 4 mm²
Conductor cross-section, solid or stranded2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), 2x 4 mm²
Conductor cross-section, finely stranded w/ ferrule2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
Mounting methodscrew and snap-on mounting onto 35 mm DIN rail according to DIN EN 50022
3RT2625-1AK65 — Durability
ParameterValue
Durability with aux. switch block (cycles, typ.)3 000 000
3RT2625-1AK65 — Environmental
ParameterValue
Operating temperature range-25 ... +60 °C
Storage temperature range-55 ... +80 °C
Installation altitude, max.2 000 m
3RT2625-1AK65 — Mechanical
ParameterValue
Width45 mm
Height135 mm
Depth155 mm
3RT2625-1AK65 — Specifications
ParameterValue
At AC4 ... 16 ms

Product details

Capacitor switching contactor, S0 frame, 110 VAC coil

The 3RT2625-1AK65: The 110 VAC 50 Hz coil (120 VAC at 60 Hz) pulls in the armature to close the main contacts, which are rated for capacitor inrush currents that would weld a standard contactor's tips.

Terminal capacity and wiring constraints

Stranded conductors: 2×(1…2.5 mm²) or 2×(2.5…10 mm²). At 40 °C ambient, a single 6 mm² conductor is permitted; at 60 °C, a single 10 mm² or 2×6 mm². The 45 mm width and 135 mm height fit standard S0 contactor spacing on the DIN rail. Depth is 155 mm, which includes the arc chamber and terminal clearance — account for this when laying out the gland plate and door swing.

Operating envelope and switching frequency

The switching frequency for capacitor duty is 180 operations per hour at 230 V, 400 V, 480 V, 500 V, and 600 V, dropping to 150 ops/h at 690 V. Auxiliary contact blocks are attachable (0 supplied) — the contactor has no built-in aux contacts. Add a SIRIUS side-mount block if feedback to the PLC or status indication is needed.

Frequently asked questions

What capacitor bank current can 3RT2625-1AK65 switch?

The contactor is designed for the high inrush current of power factor correction capacitors.

Does 3RT2625-1AK65 come with auxiliary contacts?

No, the contactor ships with 0 attachable auxiliary contacts. A separate SIRIUS side-mount auxiliary contact block must be ordered if needed.

MPN