Siemens 3RT2625-1NF35 Contactor, 95-130 V AC/DC Coil, 3-Pole

MPN3RT2625-1NF35
Active

Siemens 3RT2625-1NF35 contactor, 3-pole, screw-type terminals, 95-130 V AC/DC coil, 45 mm width, 165 mm depth, 135 mm height, DIN rail mount.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3RT2625-1NF35 — Identification
ParameterValue
Contactor frame sizeS0
3RT2625-1NF35 — Control & Coil
ParameterValue
Control supply voltage typeAC/DC
Rated value @ 50 Hz0.7 ... 1.3
Rated value @ 50 Hz95 ... 130 V
3RT2625-1NF35 — Contacts & Poles
ParameterValue
Main poles3
Main NO contacts3
Auxiliary contact reliability0.00000001
3RT2625-1NF35 — Protection & Coordination
ParameterValue
Aux. switch short-circuit protection, fusegG: 10 A (500 V, 1 kA)
3RT2625-1NF35 — Connection & Mounting
ParameterValue
Main circuit connectionscrew-type terminals
Aux. / control circuit connectionscrew-type terminals
Conductor cross-section, solid2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), 2x 4 mm²
Conductor cross-section, solid or stranded2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), 2x 4 mm²
Conductor cross-section, finely stranded w/ ferrule2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
Mounting methodscrew and snap-on mounting onto 35 mm DIN rail according to DIN EN 50022
3RT2625-1NF35 — Durability
ParameterValue
Durability with aux. switch block (cycles, typ.)3 000 000
3RT2625-1NF35 — Environmental
ParameterValue
Operating temperature range-25 ... +60 °C
Storage temperature range-55 ... +80 °C
Installation altitude, max.2 000 m
3RT2625-1NF35 — Mechanical
ParameterValue
Width45 mm
Height135 mm
Depth165 mm
3RT2625-1NF35 — Specifications
ParameterValue
At AC30 ... 50 ms

Product details

Panel fit and coil voltage

The 3RT2625-1NF35 is a 3-pole contactor with a screw-type magnet coil rated for 95-130 V at 50/60 Hz or DC. That AC/DC coil simplifies stocking — one part covers both control supply types in a panel.

Auxiliary contact ratings and switching limits

At 125 V it handles 0.9 A; at 220 V it drops to 0.3 A. These are the continuous thermal current limits — the actual switching load must stay within these per-voltage ceilings. Maximum switching frequency is 180 operations per hour at 230 V through 600 V, dropping to 150 ops/h at 690 V. The arcing time is a consistent 10 ms on both AC and DC, with operate and release times of 30-50 ms for either supply type.

Wire termination and thermal limits

For stranded wire: 2x 1-2.5 mm² or 2x 2.5-10 mm². At 40 °C ambient, one 6 mm² solid is permitted; at 60 °C, one 10 mm² or two 6 mm² solid. No auxiliary switch blocks are attachable — the 0 count means this variant ships without add-on contact blocks.

MPN
3RT2625-1NF35