Switching ratings and frequency limits
The 3RT2628-1AF05: Maximum switching frequency drops with voltage: 100 operations per hour at 230 V, 70/h at 480 V, and 36/h at 690 V — a key constraint when sizing for frequent capacitor bank cycling. The coil operates on 50 Hz AC at 110 V rated voltage, with screw-type terminals for the magnet coil connection.
For higher-current power circuits, a single 16 mm² conductor is allowed at 40 °C ambient, and a single 25 mm² at 60 °C — the larger cross-section compensates for the higher ambient temperature derating.