It mounts via screw or snap-on onto 35 mm DIN rail per DIN EN 50022, and the mounting position allows ±180° rotation on a vertical surface plus ±22.5° tilt forward or backward — useful when panel layout forces an unconventional orientation.
The contactor is rated to switch 6 A at 24 V AC and 6 A at 230 V AC, with a maximum operating rate of 150 switching cycles per hour at 230 V. At 400 V AC it handles 3 A at up to 80 cycles per hour. The arcing time falls between 10 and 20 ms — typical for this class of capacitor switching, where the inrush from discharged caps can be several times the steady-state rating. The solid conductor capacity goes up to 4 mm² on the auxiliary side and 70 mm² stranded on the main power terminals, so it accepts the cable sizes common in power factor correction sub-panels.