The 3RT5034-1AN20: The screw-type terminals on the main current circuit accept 2x (0.75…16 mm²) solid or stranded copper, or 2x (18…2 AWG). That's enough cross-section for the full rated load without pigtailing or parallel feeds.
Motor power at 60 °C — the rating that governs real use
At 60 °C ambient the contactor delivers 18 kW at 230 V, 31 kW at 400 V, and 54 kW at 690 V. These are the numbers to size against if the panel runs warm — the 40 °C ratings (not listed here) would be higher, but the 60 °C figures are the conservative design point for a closed cabinet.
Side-by-side mounting is approved, so a row of S2 contactors packs tight on the rail without thermal gaps.