The contactor carries an AC-3e rated voltage up to 690 V, meaning it handles the inductive load of a three-phase motor across that voltage range without derating the switching capacity.
Side-by-side mounting is permitted, so multiple contactors can pack tightly on the rail without derating for thermal crowding. Dimensions are 112 mm height, 55 mm width, and 115 mm depth.
Electrical ratings and switching capacity
At 400 V and 60 °C ambient, it delivers 31 kW motor power; at 690 V and 60 °C, that rises to 54 kW. The AC-3e maximum switching frequency is 1 000 operations per hour, while AC-4 (plugging/reversing) is limited to 250 operations per hour — a real constraint for high-cycle jogging applications. Coil consumption at 50 Hz is 0.42 A. The control circuit accepts a range of voltages: at 24 V rated value the coil draws 6 A, at 230 V rated value it draws 6 A, and at 400 V rated value it draws 3 A. These are inrush or holding values depending on the circuit design — verify against your specific PLC or relay output card's drive capability.