At 400 V and 60 °C ambient, this contactor is rated for 38 kW motor output; at 690 V and 60 °C, it handles 66 kW. The coil holds at 24 VDC nominal, drawing 6 A at rated value.
The 55 mm width and 130 mm depth let it fit standard S2 contactor spacing on the DIN rail — plan for that footprint when laying out a multi-contactor motor control center. Rated for AC-3e switching up to 690 V, it handles the inductive load of squirrel-cage motors during starting and running. The 63 A gL/gG fuse recommendation gives you the short-circuit coordination baseline for the branch circuit.
Mounting and wiring notes
Main circuit terminals accept 2x (0.75 to 16 mm²) solid or stranded wire, or 2x (18 to 2 AWG).