Skip to main content
Siemens 3RT5036-1AQ00 — Contactors

Siemens 3RT5036-1AQ00 SIRIUS Power Contactor, S2, 38 kW at 4

MPN3RT5036-1AQ00

Siemens SIRIUS power contactor, size S2, screw terminals, 38 kW at 400 V 60 °C, 24 A AC-3e at 690 V, 3RT5036-1AQ00.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3RT5036-1AQ00 — Identification
ParameterValue
Contactor frame sizeS2
3RT5036-1AQ00 — Ratings & Performance
ParameterValue
Rated operational current, AC-12, max.10 A
Rated value @ 400 V3 A
Rated value @ 690 V11.4 kW
Rated value @ 230 V6 A
Rated value @ 24 V6 A
Rated value @ 110 V1 A
Rated value @ 220 V0.3 A
3RT5036-1AQ00 — Control & Coil
ParameterValue
Control supply voltage typeAC
Rated value @ 50 Hz0.36
Rated value @ 50 Hz380 V
3RT5036-1AQ00 — Contacts & Poles
ParameterValue
Main poles3
Main NO contacts3
Auxiliary contact reliability1 faulty switching per 100 million (17 V, 1 mA)
3RT5036-1AQ00 — Protection & Coordination
ParameterValue
Short-circuit coordination type 1, fusefuse gL/gG: 160 A
Short-circuit coordination type 2, fusefuse gL/gG: 80 A
Aux. switch short-circuit protection, fusefuse gL/gG: 10 A
3RT5036-1AQ00 — Connection & Mounting
ParameterValue
Main circuit connectionscrew-type terminals
Aux. / control circuit connectionscrew-type terminals
Conductor cross-section, solid or stranded2x (0.75 ... 16 mm²)
Conductor cross-section, finely stranded w/ ferrule2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
Mounting methodscrew and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022
Side-by-side mountingYes
3RT5036-1AQ00 — Durability
ParameterValue
Durability (operating cycles, typ.)10 000 000
Durability with aux. switch block (cycles, typ.)10 000 000
3RT5036-1AQ00 — Environmental
ParameterValue
Operating temperature range-25 ... +60 °C
Storage temperature range-55 ... +80 °C
Installation altitude, max.2 000 m
3RT5036-1AQ00 — Mechanical
ParameterValue
Width55 mm
Height112 mm
Depth115 mm
3RT5036-1AQ00 — Specifications
ParameterValue
At AC5 000 1/h

Product details

Its AC-3e rating of 24 A at 690 V means it handles three-phase induction motors up to that current in the most common switching duty — starting and stopping a running motor. At 400 V and 60 °C ambient, it delivers 38 kW, which is the number most panel builders size against for a 400 V line. Screw-type terminals on both the main and auxiliary/control circuits accept up to 16 mm² (2x) solid or stranded wire, or 2x 18–2 AWG. The 55 mm width and 115 mm depth mean it fits standard 200 mm deep enclosures with room for side-by-side mounting.

Where it goes and what it needs

Rated insulation voltage is 690 V, so it's suited for 400 V and 690 V line-to-line systems. The operating temperature range of -25 to +60 °C covers most indoor panel environments; storage range of -55 to +80 °C handles warehouse extremes. Mounting position allows +/-180° rotation on a vertical surface and tilting forward/backward by +/-22.5°, giving flexibility in tight enclosures.

The part carries the SIRIUS brand, which is Siemens' standard industrial contactor family with broad UL/CSA/CE acceptance across markets.

Frequently asked questions

What are the key dimensions for panel fit?

Width is 55 mm, height is 112 mm, depth is 115 mm. It mounts on 35 mm DIN rail with screw and snap-on fastening, and side-by-side mounting is allowed.

What motor power can this contactor handle?

At 400 V and 60 °C ambient, it is rated for 38 kW. At 690 V and 60 °C, it handles 66 kW. The AC-3e current rating is 24 A at 690 V.

What compliance documentation is available?

RoHS compliance is confirmed with a substance prohibition date of March 1, 2017. The SIRIUS series typically carries UL, CSA, and CE approvals for global panel acceptance.

MPN
3RT5036-1AQ00