Skip to main content
Siemens 3RT5044-1AM00 — Contactors

Siemens 3RT5044-1AM00 SIRIUS Power Contactor, S3, 70 mm, 100

MPN3RT5044-1AM00

Siemens SIRIUS power contactor, size S3, 3RT5044-1AM00, 70 mm width, rated insulation voltage 1000 V, screw-type terminals, screw and snap-on DIN-rail mounting.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

3RT5044-1AM00 — Identification
ParameterValue
Contactor frame sizeS3
3RT5044-1AM00 — Ratings & Performance
ParameterValue
Rated operational current, AC-12, max.10 A
Rated value @ 400 V3 A
Rated value @ 690 V18.6 kW
Rated value @ 230 V6 A
Rated value @ 24 V6 A
Rated value @ 110 V1 A
Rated value @ 220 V0.3 A
3RT5044-1AM00 — Control & Coil
ParameterValue
Control supply voltage typeAC
Rated value @ 50 Hz0.26
Rated value @ 50 Hz220 V
3RT5044-1AM00 — Contacts & Poles
ParameterValue
Main poles3
Main NO contacts3
Auxiliary contact reliability1 faulty switching per 100 million (17 V, 1 mA)
3RT5044-1AM00 — Protection & Coordination
ParameterValue
Short-circuit coordination type 1, fusefuse gL/gG: 250 A
Short-circuit coordination type 2, fusefuse gL/gG: 125 A
Aux. switch short-circuit protection, fusefuse gL/gG: 10 A
3RT5044-1AM00 — Connection & Mounting
ParameterValue
Main circuit connectionscrew-type terminals
Aux. / control circuit connectionscrew-type terminals
Conductor cross-section, solid or stranded2x (2.5 ... 16 mm²)
Conductor cross-section, finely stranded w/ ferrule2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
Mounting methodscrew and snap-on mounting onto 35 mm and 75 mm DIN rail
Side-by-side mountingYes
3RT5044-1AM00 — Durability
ParameterValue
Durability (operating cycles, typ.)10 000 000
Durability with aux. switch block (cycles, typ.)10 000 000
3RT5044-1AM00 — Environmental
ParameterValue
Operating temperature range-25 ... +60 °C
Storage temperature range-55 ... +80 °C
Installation altitude, max.2 000 m
3RT5044-1AM00 — Mechanical
ParameterValue
Width70 mm
Height146 mm
Depth139 mm
3RT5044-1AM00 — Specifications
ParameterValue
At AC5 000 1/h

Product details

Rated insulation voltage is 1000 V, and it carries motor power ratings of 34 kW at 230 V, 59 kW at 400 V, and 102 kW at 690 V (all at 60 °C ambient). That puts it squarely in the range for medium-horsepower three-phase induction motors on 400 V or 690 V distribution.

The contactor measures 146 mm high, 70 mm wide, and 139 mm deep. That 70 mm width is the key panel-spacing number — it dictates how many units fit across a given DIN-rail length. That helps when routing cables in a tight enclosure.

Main circuit terminals accept 2x (2.5 to 16 mm²) solid or stranded copper, or 2x (10 to 1/0 AWG). Minimum permissible conductor size is 35 mm² at both 40 °C and 60 °C — that's the cross-section needed to carry the rated current without exceeding terminal temperature rise. Auxiliary contacts are rated for switching: 6 A at 24 V and 230 V, 3 A at 400 V, 1 A at 110 V, 0.3 A at 220 V. The contactor accepts an auxiliary switch block extension, so you can add more signal contacts without replacing the base unit.

Frequently asked questions

What are the key dimensions for panel layout?

The contactor is 146 mm high, 70 mm wide, and 139 mm deep. The 70 mm width is the critical dimension for DIN-rail spacing. Side-by-side mounting is permitted.

What compliance documentation is available?

The part carries a substance prohibition date of 03/01/2017, indicating RoHS and REACH compliance. Rated insulation voltage is 1000 V, and pollution degree 3 is specified for industrial environments.

What wire sizes does the main terminal accept?

Main circuit screw terminals accept 2x (2.5 to 16 mm²) solid or stranded, or 2x (10 to 1/0 AWG). Minimum permissible conductor is 35 mm² at both 40 °C and 60 °C ambient.

MPN
3RT5044-1AM00