It mounts on 35 mm or 75 mm standard DIN rail via screw or snap-on fastening, with ±180° rotation and ±22.5° tilt possible on a vertical surface — useful when panel layout forces an unconventional orientation. Frame size S3 and a 70 mm width mean it occupies two standard 35 mm DIN-rail slots side by side, and side-by-side mounting is explicitly permitted — no derating gap required between units.
Motor power ratings at 60 °C ambient: 38 kW at 230 V, 66 kW at 400 V, and 114 kW at 690 V — these are the numbers that govern real motor sizing, not the lower 25.4 kW at 690 V figure which applies under a different condition. At 40 °C the conductor cross-section minimum is 50 mm²; at 60 °C it drops to 35 mm², reflecting the thermal derating curve. Switching frequency limits: 900 operations/hour under AC-1 resistive load, 850/h under AC-3 motor starting, 250/h under AC-4 plugging/reversing, and 1,000/h for DC loads. The control supply accepts 110 VDC nominal; at that voltage the coil draws 1 A. At 24 VDC it draws 6 A, at 220 VDC 0.3 A, and at 230 VDC 6 A.
Termination and protection
Main and control circuits use screw-type terminals. Main contacts accept 2x (2.5...16 mm²) solid or stranded, or 2x (10...1/0) AWG. The recommended short-circuit protection is a gL/gG fuse rated 160 A — that's the fuse size to coordinate with upstream selectivity. The contactor supports auxiliary switch extension (product extension auxiliary switch: yes), so you can add feedback contacts or status indication without replacing the base unit.