Dimensions are 210 mm height, 145 mm width, 202 mm depth. The main circuit uses screw-type terminals accepting 2/0 to 500 kcmil AWG or 185 mm² minimum conductor at both 40 °C and 60 °C.
Electrical Ratings & Duty Cycles
Rated insulation voltage is 1 000 V. The contactor carries a mechanical life of 10 000 000 operations typical. Switching frequency varies by duty: 2 000 operations per hour for both AC and DC general use, up to 800 1/h in AC-1 (resistive) duty, 700 1/h in AC-3 (motor starting), and 130 1/h in AC-4 (plugging/reversing). The coil circuit is rated for 6 A at 24 V, 1 A at 110 V, 0.3 A at 220 V, 6 A at 230 V, and 3 A at 400 V. A built-in varistor surge suppressor handles coil transients — no external snubber needed for standard PLC or relay outputs.