It carries a 24 VAC coil rated for both 50 Hz and 60 Hz operation, drawing 6 A at 24 V. The contactor is rated for motor switching up to 10.5 kW at 400 V and 18 kW at 690 V, with a maximum AC-3 switching voltage of 690 V. Insulation voltage is rated at 690 V, and the unit is suitable for pollution degree 3 environments.
Side-by-side mounting is supported, allowing dense packing in multi-contactor panels. Screw-type terminals on the main current circuit accept 2x (0.5 to 1.5 mm²), 2x (0.75 to 2.5 mm²), or 2x 4 mm² solid or stranded wire. Minimum permissible conductor size is 2.5 mm² at both 40 °C and 60 °C ambient.
Duty Ratings and Switching Frequency
Rated for 10,000 operations per hour at AC, with category-specific maximums: 1,000/h for AC-1 resistive loads, 750/h for AC-3 and AC-3e motor switching, and 250/h for AC-4 reversing or inching duty. Auxiliary contact ratings at various voltages: 10 A at 230 V, 6 A at 24 V, 3 A at 400 V, 1 A at 690 V, 1 A at 110 V, and 0.3 A at 220 V. These cover typical control-circuit loads for signaling and interlocking.
Substance prohibition date is May 1, 2012, indicating RoHS compliance per EU directives.