It mounts via screw and snap-on onto 35 mm DIN rail per DIN EN 50022, and its 45 mm width and 73 mm depth keep the panel fill factor tight — three of these sit in the space of a single 4-pole breaker.
Rated AC-3 at 690 V maximum, this contactor handles motor switching up to 6 kW at 230 V, 10.5 kW at 400 V, and 18 kW at 690 V — all at 60 °C ambient. The AC-3 duty cycle maxes at 750 operations per hour, so it's fine for frequent start-stop on conveyors or pumps, but not for jogging or inching at high rates. Coil draw is 0.25 A at both 50 Hz and 60 Hz, which is low enough that a standard 24 VDC PLC output can drive it through an interposing relay without a separate power supply for the coil bus.
Screw-type terminals on the main circuit accept 2x (0.5 to 1.5 mm²), 2x (0.75 to 2.5 mm²), or 2x 4 mm² solid or stranded copper. Side-by-side mounting is permitted, which keeps multi-contactor groups dense.