Skip to main content
Siemens 3RT6015-1KF41 — Contactors

Siemens 3RT6015-1KF41 SIRIUS Contactor, 110 V Coil, Size S00

MPN3RT6015-1KF41

Siemens SIRIUS 3RT6015-1KF41 coupling contactor, Size S00, 110 V AC coil, screw-type terminals, 45 x 57.5 x 73 mm, DIN EN 50022 snap-on mounting.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3RT6015-1KF41 — Identification
ParameterValue
Contactor frame sizeS00
3RT6015-1KF41 — Ratings & Performance
ParameterValue
Rated operational current, AC-12, max.10 A
Rated value @ 400 V3 A
Rated value @ 690 V1 A
Rated value @ 230 V10 A
Rated value @ 24 V6 A
Rated value @ 110 V1 A
Rated value @ 220 V0.3 A
3RT6015-1KF41 — Control & Coil
ParameterValue
Control supply voltage typeDC
3RT6015-1KF41 — Contacts & Poles
ParameterValue
Main poles3
Main NO contacts3
Auxiliary contact reliability1 faulty switching per 100 million (17 V, 1 mA)
3RT6015-1KF41 — Protection & Coordination
ParameterValue
Short-circuit coordination type 1, fusegL/gG LV HRC 3NA, DIAZED 5SB, NEOZED 5SE: 35 A
Short-circuit coordination type 2, fusegL/gG LV HRC 3NA, DIAZED 5SB, NEOZED 5SE: 20 A
Aux. switch short-circuit protection, fusefuse gL/gG: 10 A
3RT6015-1KF41 — Connection & Mounting
ParameterValue
Main circuit connectionscrew-type terminals
Aux. / control circuit connectionscrew-type terminals
Conductor cross-section, solid or stranded2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), 2x 4 mm²
Conductor cross-section, finely stranded w/ ferrule2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
Mounting methodscrew and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022
Side-by-side mountingYes
3RT6015-1KF41 — Durability
ParameterValue
Durability (operating cycles, typ.)30 000 000
3RT6015-1KF41 — Environmental
ParameterValue
Operating temperature range-25 ... +60 °C
Storage temperature range-55 ... +80 °C
Installation altitude, max.2 000 m
3RT6015-1KF41 — Mechanical
ParameterValue
Width45 mm
Height57.5 mm
Depth73 mm

Product details

Motor switching capacity and duty cycles

The 3RT6015-1KF41: The AC-3 maximum switching frequency is 750 1/h; AC-4 drops to 250 1/h for inching or plugging duty. The built-in suppressor diode handles the coil's inductive kickback, so no external snubber is needed for the 110 V coil.

Environmental and compliance specs

The substance prohibitance date of 05/01/2012 aligns with RoHS compliance milestones.

Frequently asked questions

What motor power can the 3RT6015-1KF41 switch at 400 V?

At 400 V and 60 °C ambient, the contactor is rated for 10.5 kW motor load in AC-3 duty. At 230 V it handles 6 kW, and at 690 V it handles 18 kW — these are the Size S00 frame's real-world motor ratings.

Does the 3RT6015-1KF41 include a surge suppressor?

Yes, the design includes a built-in suppressor diode across the coil. This eliminates the need for an external snubber on the 110 V coil circuit.