It switches motor loads up to 7.5 kW at 230 V (60 °C), 13 kW at 400 V (60 °C), and 22 kW at 690 V (60 °C).
Side-by-side mounting is permitted, so multiple contactors pack tightly on the rail without mandatory spacing gaps.
The AC-3 motor-switching rating at 690 V maximum covers most 400 V and 690 V industrial loads. The 60 °C derated power figures (7.5 kW at 230 V, 13 kW at 400 V, 22 kW at 690 V) are the ones to size against in a warm cabinet — the contactor is rated for continuous operation at that ambient. Mechanical life is 30 million operations typical; electrical life at AC-3 is 750 cycles per hour maximum, with a 1,000/hour ceiling at AC-1 resistive loads.