Skip to main content
Siemens 3RT6016-1AK21 — Contactors

Siemens 3RT6016-1AK21 SIRIUS Contactor, 10 A AC-3, 230 V Coi

MPN3RT6016-1AK21

Siemens SIRIUS S00 power contactor, 3RT6016-1AK21, 10 A AC-3 at 230 V, 690 V max, 230 V AC coil, screw terminals, 45 mm width, DIN rail mount.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

3RT6016-1AK21 — Identification
ParameterValue
Contactor frame sizeS00
3RT6016-1AK21 — Ratings & Performance
ParameterValue
Rated operational current, AC-12, max.10 A
Rated value @ 400 V3 A
Rated value @ 690 V1 A
Rated value @ 230 V10 A
Rated value @ 24 V6 A
Rated value @ 110 V1 A
Rated value @ 220 V0.3 A
3RT6016-1AK21 — Control & Coil
ParameterValue
Control supply voltage typeAC
Rated value @ 50 Hz0.25
Rated value @ 50 Hz120 V
3RT6016-1AK21 — Contacts & Poles
ParameterValue
Main poles3
Main NO contacts3
Auxiliary contact reliability1 faulty switching per 100 million (17 V, 1 mA)
3RT6016-1AK21 — Protection & Coordination
ParameterValue
Short-circuit coordination type 1, fusegL/gG LV HRC 3NA, DIAZED 5SB, NEOZED 5SE: 35 A
Short-circuit coordination type 2, fusegL/gG LV HRC 3NA, DIAZED 5SB, NEOZED 5SE: 20 A
Aux. switch short-circuit protection, fusefuse gL/gG: 10 A
3RT6016-1AK21 — Connection & Mounting
ParameterValue
Main circuit connectionscrew-type terminals
Aux. / control circuit connectionscrew-type terminals
Conductor cross-section, solid or stranded2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), 2x 4 mm²
Conductor cross-section, finely stranded w/ ferrule2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
Mounting methodscrew and snap-on mounting onto 35 mm DIN rail according to DIN EN 50022
Side-by-side mountingYes
3RT6016-1AK21 — Durability
ParameterValue
Durability (operating cycles, typ.)30 000 000
Durability with aux. switch block (cycles, typ.)10 000 000
3RT6016-1AK21 — Environmental
ParameterValue
Operating temperature range-25 ... +60 °C
Storage temperature range-55 ... +80 °C
Installation altitude, max.2 000 m
3RT6016-1AK21 — Mechanical
ParameterValue
Width45 mm
Height57.5 mm
Depth73 mm
3RT6016-1AK21 — Specifications
ParameterValue
At AC10 000 1/h

Product details

SIRIUS S00 power contactor — 10 A AC-3, 230 V coil

The Siemens 3RT6016-1AK21 is a SIRIUS S00 power contactor rated for AC-3 switching at 10 A at 230 V, with a maximum operating voltage of 690 V AC-3/AC-3e. The 230 V AC coil draws 10 A at rated value, and the contactor handles motor loads up to 7.5 kW at 230 V and 13 kW at 400 V at 60 °C ambient. Screw-type terminals on the main circuit accept 2x (0.5 to 2.5 mm²) solid or stranded wire, with a minimum permissible 4 mm² at 40 °C.

Pollution degree 3 suits industrial environments with conductive contamination.

Switching performance and compliance

Rated for 10,000 switching cycles per hour at AC load, with maximum rates of 1,000/h for AC-1, 750/h for AC-3/AC-3e, and 250/h for AC-4. Mechanical endurance is 30 million operations typical. The contactor meets RoHS compliance with substance prohibition date of May 1, 2012.

Frequently asked questions

What are the key ratings for 3RT6016-1AK21?

AC-3 rated current is 10 A at 230 V, with maximum AC-3/AC-3e voltage of 690 V. Motor power at 60 °C is 7.5 kW at 230 V, 13 kW at 400 V, and 22 kW at 690 V. The 230 V AC coil draws 10 A at rated value.

Where can I buy 3RT6016-1AK21?

This part is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time.

Will 3RT6016-1AK21 drop into a panel specified around 3RT6015-1AF02?

Both are SIRIUS S00 contactors with the same 45 mm width and DIN-rail mounting, so the footprint is identical. The main difference is the coil voltage — 3RT6016-1AK21 uses a 230 V AC coil, while 3RT6015-1AF02 uses a different coil voltage. Verify the coil voltage matches your control circuit before swapping.

What compliance documentation does Siemens provide for 3RT6016-1AK21?

RoHS compliance is confirmed with a substance prohibition date of May 1, 2012. The contactor is designed to meet IEC/EN standards for industrial control equipment (pollution degree 3, rated insulation voltage 690 V).

MPN
3RT6016-1AK21