SIRIUS S00 power contactor — 3RT6016-1AK62
Rated for AC-3 duty up to 690 V, it delivers 7.5 kW at 230 V, 13 kW at 400 V, and 22 kW at 690 V at 60 °C ambient — covering common European and North American motor voltage tiers.
Terminals and wiring
Main current circuit uses screw-type terminals accepting 2x (0.5...1.5 mm²), 2x (0.75...2.5 mm²), or 2x 4 mm² solid or stranded conductors. Minimum permissible cross-section is 4 mm² at 40 °C and 2.5 mm² at 60 °C — wire down for higher ambient, not up.