It switches motor loads up to 7.5 kW at 230 V, 13 kW at 400 V, and 22 kW at 690 V — the 400 V figure is the one most panel builders will size against for standard three-phase induction motors across Europe and Asia. Mechanical life is rated at 30,000,000 operating cycles, with maximum switching rates of 10,000 cycles per hour on general AC duty, 1,000/h under AC-1 (resistive loads), 750/h under AC-3 (squirrel-cage motors), and 250/h under AC-4 (plugging/inching).
Width is 45 mm, depth 73 mm, height 57.5 mm — three units fit in a standard 145 mm wide DIN section with room for a terminal block alongside. Side-by-side mounting is permitted with no derating gap. That covers most enclosure layouts without needing a special bracket. Screw-type terminals on the main circuit accept 2x (0.5 to 1.5 mm²), 2x (0.75 to 2.5 mm²), or 2x 4 mm² solid or stranded. Minimum cross-section at 40 °C ambient is 4 mm²; at 60 °C ambient it drops to 2.5 mm² — a useful derating rule for panels running hot near drives or transformers.