Rated for AC-3 duty up to 690 V, this contactor delivers 13 kW at 400 V and 60 °C ambient, and 22 kW at 690 V at the same temperature — the derated figures at 60 °C are what govern in a warm enclosure, not the 40 °C headline.
The screw-type terminals on the main circuit accept 2x (0.5 to 1.5 mm²), 2x (0.75 to 2.5 mm²), or 2x 4 mm² solid or stranded conductors. At 60 °C the minimum permissible cross-section is 2.5 mm² — that's the wire size you need to carry the rated current without exceeding the terminal temperature rise. Mounting orientation: +/-180° rotation on vertical surface, tilt forward/backward +/-22.5°. Depth 73 mm, height 57.5 mm.
RoHS compliance date is 05/01/2012. Insulation voltage rated 690 V, pollution degree 3 for industrial environments.
Mechanical endurance and switching frequency
Maximum electrical switching rate at AC-3 is 750 operations per hour, at AC-4 it is 250 per hour.