3RT6017-1BB41 — Identification
ParameterValue
Contactor frame sizeS00
3RT6017-1BB41 — Ratings & Performance
ParameterValue
Rated operational current, AC-12, max.10 A
Rated value @ 400 V3 A
Rated value @ 690 V1 A
Rated value @ 230 V10 A
Rated value @ 24 V6 A
Rated value @ 110 V1 A
Rated value @ 220 V0.3 A
3RT6017-1BB41 — Control & Coil
ParameterValue
Control supply voltage typeDC
3RT6017-1BB41 — Contacts & Poles
ParameterValue
Main poles3
Main NO contacts3
Auxiliary contact reliability1 faulty switching per 100 million (17 V, 1 mA)
3RT6017-1BB41 — Protection & Coordination
ParameterValue
Short-circuit coordination type 1, fusegL/gG LV HRC 3NA, DIAZED 5SB, NEOZED 5SE: 35 A
Short-circuit coordination type 2, fusegL/gG LV HRC 3NA, DIAZED 5SB, NEOZED 5SE: 20 A
Aux. switch short-circuit protection, fusefuse gL/gG: 10 A
3RT6017-1BB41 — Connection & Mounting
ParameterValue
Main circuit connectionscrew-type terminals
Aux. / control circuit connectionscrew-type terminals
Conductor cross-section, solid or stranded2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), 2x 4 mm²
Conductor cross-section, finely stranded w/ ferrule2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
Mounting methodscrew and snap-on mounting onto 35 mm DIN rail according to DIN EN 50022
Side-by-side mountingYes
3RT6017-1BB41 — Durability
ParameterValue
Durability (operating cycles, typ.)30 000 000
Durability with aux. switch block (cycles, typ.)10 000 000
3RT6017-1BB41 — Environmental
ParameterValue
Operating temperature range-25 ... +60 °C
Storage temperature range-55 ... +80 °C
Installation altitude, max.2 000 m
3RT6017-1BB41 — Mechanical
ParameterValue
Width45 mm
Height57.5 mm
Depth73 mm

Product details

It switches motor loads up to 7.5 kW at 400 V AC-3e (60 °C ambient) and 22 kW at 690 V AC-3e — the 690 V figure is the one to watch for 480 V or 600 V class installations where the contactor sees the full line voltage.

The AC-3e rated voltage max is 690 V, which covers 400 V and 480 V systems with headroom — the contactor is not limited to 400 V. At 400 V and 60 °C, the motor power rating is 13 kW; at 690 V it reaches 22 kW. The contactor accepts 2x 4 mm² solid or stranded wire on the main terminals, with a minimum permissible cross-section of 2.5 mm² at 60 °C.

Fastens via screw and snap-on to 35 mm DIN rail (DIN EN 50022). The S00 size means it occupies the same footprint as other S00 accessories (overload relays, auxiliary contact blocks).

Frequently asked questions

What are the key motor power ratings for 3RT6017-1BB41?

At 400 V and 60 °C ambient, the contactor is rated for 13 kW AC-3e; at 690 V and 60 °C, it handles 22 kW. The 230 V rating at 60 °C is 7.5 kW.

What is the width and depth of 3RT6017-1BB41?

Width is 45 mm, depth is 73 mm, height is 57.5 mm — the S00 frame size.